CN-8013 CC-Link Slave Coupler

C Series Remote I/O System

The C Series is a remote I/O system composed of a network adapter module and extended I/O modules. The network adapter module is responsible for fieldbus communication and can establish communication with the master controller or host computer software.

The Odot CN-8013 is a CC-Link adapter designed for simplicity. Thanks to its versatility, it seamlessly integrates into your automation systems, ensuring high-speed data transmission and uncompromising reliability. It supports standard CC-Link Ver.2 communication and allows real-time monitoring of the communication status of IO modules.

Adapter Hardware Parameters

  • System Power:
    • Nominal: 24Vdc, Range: 19.2-28.8Vdc
    • Reverse polarity protection: Yes
    • Power consumption: 110mA@24Vdc
    • Internal Bus Power Supply Current: Max: 2.5A@5Vdc
    • Isolation: Isolation between system power supply and field power supply
    • Power supply: Nominal: 24Vdc, Range: 19.2-28.8Vdc
    • Maximum field current: 8A DC
  • Supported IO Modules: 32 units
  • Wiring: Max: 1.0mm² (AWG 17)
  • Mounting Type: 35mm DIN rail
  • Dimensions: 115 x 51.5 x 75mm
  • Weight: 130g

Environmental Specifications

  • Operating temperature: -35 ~ 70℃
  • Operating humidity: 5%-95% (non-condensing)
  • Protection class: IP20

CC-Link Parameters

  • Protocol: CC-Link Ver.2
  • Station type: Remote station
  • Number of occupied logical stations: 1, 2, 3, 4
  • Extended cycle configuration: 1, 2, 4, 8 times
  • IO data capacity:
    • RX/RY capacity (bits): max. 896
    • RWr/RWw capacity (word): max. 128
  • Transmission speed (Baud Rate): 156K / 625K / 2.5M / 5M / 10Mbps
  • Node station number (Station No.): 1~64 (configured via DIP switch). If the DIP switch value is not between 1 and 64, the mandatory station number is 1.
  • Interface: 5-pin screw terminal
  • Maximum bus length: 1200m (156kbps)
  • Termination resistance: 120 ohm